• Text

MRC-250HWN1-R(C)

MODEL NUMBER: MRC-250

  • Design flexibility
  • Durable construction
  • Reliable scroll compressor
  • Adjustable pulley
  • Multi-protection design
  • System self-diagnostic function

Energy Efficient

  • Pre-heats or pre-cools the fresh air coming into you home so your air conditioning system doesn’t have to work as hard to reach comfortable temperature

Healthy Home

  • The fresh air introduced into your home is filtered using specially treated paper filters to improving air quality for allergy and asthma sufferers

Better Air Quality

  • Brings in fresh outdoor air and circulates it in your home. Air quality is improved because odours and other pollutants are removed from your home

Built-in Drain Pump

  • The drain pump can lift the condensate water up to 750mm This issue is in all places, make sure you keep correct values for the water-lift height (eg. 750mm)
Power supply 380-415V,3Ph~,50Hz
Cooling Cooling capacity '300,000Btu/h
Cooling capacity 88Kw
Power input 28.9Kw
Heating Heating capacity '330,000Btu/h
Heating capacity 97Kw
Power input 30.3Kw
Max. input consumption 38.5Kw
Max. current 74.3A
Performance Indoor air flow '10,000CFM
ESP Default: 110; 0 - 350Pa
EER 10.4Btu/h.W
COP 10.9Btu/h.W
Indoor coil Number of rows 4
Fin spacing 1.6mm
Fin type Hydrophilic aluminum fin
Tube diameter Φ8mm
Tube type Inner grooved copper pipe
Indoor fan Type / Quantity Centrifugal / 2
Drive type Belt
Motor quantity 1
Motor model YE2-132S-4-5.5KW
Motor capacitor  \
Motor input  \
Motor speed '1,440RPM
Compressor Type / Quantity Scroll / 2
Model SH161A4ALC
Brand Danfoss
Capacity '38,800W
Input '12,145W
RLA 23.6A
LRA 158A
Refrigerant oil '3,300ml
Outdoor coil Number of rows 3+2+3+2
Fin spacing 1.6+1.6+1.6+1.6mm
Fin type Hydrophilic aluminum fin
Tube diameter Φ8+Φ8mm
Tube type Inner grooved copper pipe
Outdoor fan Type Axial
Quantity 2
Drive type Direct
Motor quantity 2
Motor model YS1500-6-2
Motor capacitor  \
Motor input  \
Fan speed 910RPM
Refrigerant Type R410A
Volume 8.7+8.7Kg
Control Capillary
Sound pressure level 76.8dB(A)
Wired controller KJR-12B/dP(T)-E(B)
Centralized controller (Optional) Yes
Ambient temperature (Cooling) '10 - 46°C
Ambient temperature (Heating) -9 - 24°C
System stage 2
Dimensions Net (W×H×D) 2,320×1,245×2,220mm
Packing (W×H×D) 2,330×1,275×2,230mm
Weight Net 940Kg
Gross 970Kg
Nominal ton 30(Ton)